HV Phasing Sticks
HV Phasing sticks Introduction
ZC-820 HV Phasing sticks up to 110 kV AC, used in power lines, phase tests and phase sequence tests for substations, with functions of phase testing, phase sequence testing, electrical inspection. With strong anti-interference ability, in line with (EMC) standards, adapt to a variety of electromagnetic interference occasions. High voltage phase signal will be taken out by the collector, discharge directly after treatment. Received by instrument and compare the phase, and identify the results. This product is wireless transmission, safe, reliable, fast and accurate, adapt to a variety of phase testing occasions. Its main advantage is without the wire which connect two grids (power source) , distance up to 200M and could trough enclosure or partition plate, improve the safety, without the limitation by terrain and the structure of the equipment , easy to operate, only need one person to operate and one person to supervise.
Features
1. Use high capacitive non-maintenance lithium battery to supply power, special for field test.
2. Long transmission distance, up to 200M.
3. LCD display phase ,waveform, frequency , safe and reliable.
4. Telescopic insulation bar, easy to use.
5. Portable receiver with non-skid treatment.
6. Uses advanced technique, small in volume, light in weight
HV Phasing sticks Parameters
Semi-Automatic PET Bottle Blowing Machine Bottle Making Machine Bottle Moulding Machine
PET Bottle Making Machine is suitable for producing PET plastic containers and bottles in all shapes.
It is widely used to produce the carbonated bottle, mineral water, pesticide bottle oil bottle cosmetics, wide-mouth bottle and hot fill bottle etc.
Beverage bottle, cosmetic bottle, medicine bottle, jar etc.
Lorem Ipsum is simply dummy text of the printing and typesetting industry. Lorem Ipsum has been the industry's standard dummy text ever since the 1500s, when an unknown printer took a galley of type and scrambled it to make a type specimen book.
Accuracy of phase difference | error≤5 |
Self correcting error | <2 |
Frequency accuracy | ±0.1HZ |
The measured voltage level of this product is | 0.22~220KV |
The transmitter and the receiving host transmit a distance greater than 130 meters, the maximum distance between the two transmitters is about 260 meters; | |
The judge (in-phase and out of phase) using a standard phase difference of more than 30 degrees out of phase, the phase difference of <30 degrees for phase; | |
The voice prompt, male and female "event" "out of phase" note"; | |
At the same time, the screen shows the phase difference, frequency, waveform and loss of two lines; | |
Host display battery power, half an hour without the operation of automatic shutdown; | |
Two transmitters and receivers are built in rechargeable lithium battery; |
Table 1 insulation rod mechanical , electrical parameters
Item | Unit | Index |
Martin heart resistance (portrait) | ℃ | >200 |
Impact resistance (portrait) | MPa/cm | >147 |
Buckling resistance (portrait) | MPa | >343 |
Surface resistivity (after water-immersed) | Ω | >10x1011 |
Volume resistivity (normal) | Ω/cm | >10x1031 |
Table 2 voltage withstand measurement parameters for insulation rod
Voltage (kV) | Length (m) | Frequency voltage (kV) Standard value | Frequency voltage (kV) Measurement value | Time (min) | Results |
6-10 | 1.5 | 44 | 44 | 1~5 | Q |
35 | 2.4 | 80 | 80 | 1~5 | Q |
66~110 | 2.8 | 254 | 254 | 1~5 | Q |