50kv Hipot Test Equipment VLF Hipot Test Kit
I. Hipot Test Equipment VLF Hipot Test Kit Series
Model no | Rated Voltage/current | Load Carrying Capacity | Power FuseTube | Product Structure and Weight |
ZC-524-30 | 30kV/20mA (Peak) | 0.1Hz,≤1.1µF | 5A | Controller:4㎏ Booster: 25㎏ |
0.05Hz,≤2.2µF | ||||
0.02Hz,≤5.5µF | ||||
ZC-524-50 | 50kV/30mA (Peak) | 0.1Hz,≤1.1µF | 15A | Controller:4㎏ Booster: 50㎏ |
0.05Hz,≤2.2µF | ||||
0.02Hz,≤5.5µF | ||||
ZC-524-80 | 80kV/30mA (Peak) | 0.1Hz,≤0.5µF | 20A | Controller:4㎏ Booster Grade 1(30kV):25㎏ Booster Grade 2(50kV):50㎏ |
0.05Hz,≤1µF | ||||
0.02Hz,≤2.5µF |
II. Hipot Test Equipment VLF Hipot Test Kit Important tips
1. Power supply requirement: AC50Hz, 220V, stability of frequency: fluctuation less than 0.5%
2. When using it, the capacitance of the sample should not exceed the rated capacity of the instrument. The overlow capacitance of the sample will affect the output wave form. If the capacitance is less than 0.05µF, the instrument cannot output normally.
3. When using it, it is prohibited to boost voltage without load, or to connect with resistive load.
III. Hipot Test Equipment VLF Hipot Test Kit Product brief
★ Data of current, voltage, wave form can be directly sampled at high voltage side, so the data is real and accurate.
★ Overvoltage protection: If the output exceeds the set limit of voltage, the instrument will shut-down to protect itself, the actuation time is less than 20ms.
★ Overcurrent protection: it is high-low voltage dual protection in the design, the accurate shut-down protection can be made according to the set value at high voltage side; If the current on low voltage side exceeds the rated current, the instrument will take shut-down protection, the actuation time are both less than 20ms.
★ A high voltage output protective resistor is provided in the voltage boost body in the design and this eliminates the need of additional protective resistor connected outside.
IV. Hipot Test Equipment VLF Hipot Test Kit Technical parameters
1. Output voltage ratings: See Details of Table 1
2. Output frequency: 0.1Hz, 0.05Hz, 0.02Hz
3. Measurement accuracy: 3%
4. Positive and negative voltage peak errors: ≤ 3%
5. Voltage wave form distortion: ≤ 5%
6. Use condition: indoor and outdoor; temperature: -10℃∽+40℃
Humidity: ≤ 85%RH
7. Power: AC50Hz, 220V ±5%