Partial Discharge Tester

Partial Discharge Tester
Partial Discharge Tester

Partial discharge does not cause the electric discharge of a completely short-circuited electrode. Such discharge usually has a very small amplitude value, but it will certainly cause the continuous deterioration of the property of the insulation layer and finally cause electric equipment fault.The non-intrusive partial discharge detection, as a convenient and simple method, is used for identifying the potential insulation faults which may cause power cutoff or personal injury.


The partial discharge emits energy in following manners:

Electromagnetic energy: radio wave, light and heat;Sound energy: sound wave and ultrasonic wave;Gas: ozone and nitric oxide.

he most practical non-intrusive detection technologies are all based on the detection of the high-frequency signals and the ultrasonic signals in the electromagnetic spectrum.

The product is an instrument which has simple operation and is specially developed for detecting the activities of electromagnetic waves and ultrasonic waves.


Product Parameters

Model:

ZC-830

Applicable scope

the non-intrusive mode is adopted to detect and locate the partial discharge defects of the high-voltage electric equipment.

Detection principle

UHF (Ultra High Frequency) method, UA (Ultrasonic Analysis) method and TEV (Transient Earth Voltage) method

Detection frequency band

the UHF detection frequency band is 300~2000(MHz) and the ultrasonic detection frequency band is 20~200(KHz).

Measurement range

the UHF measurement range is -80~10dBm and the ultrasonic measurement range is -90~80dB.

Sensitivity

the minimum sensitivity is 10pC (specifically determined by the distance between the sensor and the discharge source).

Sensor:

a) UHF sensor: 300~2000(MHz), with directional reception characteristic;

b) Ultrasonic sensor: 20~200(kHz);

c) EV (Transient Earth Voltage) sensor: 5 ~ 100MHz.

Embedded ultrasonic sensor and TEV & UA integrated sensor

such components as transformer dedicated sensor, GIS dedicated sensor and cable dedicated sensor can be selected;

Software function:

a) Continuously detect UHF, TEV and ultrasonic signals to judge whether there is any partial discharge;

b) Display the variation tendency of the detected signal in a real-time manner to intuitionally judge the development of the partial discharge signal;

c) Field data storage function;

Complete configuration

host machine, sensor, AC adapter, connecting cable and transport case

Screen display

high-contrast 3.5”TFT color screen.

Data storage

4000 groups of test data can be stored.

Working power supply

embedded 8.4V lithium battery for 8h’s continuous operation

Power supply

input 100-240VAC, output 8.4V/3A, charging time 3~4h.

Boundary dimension

220 * 100 * 40

Instrument weight

1.5kg

Environment temperature

-25℃~45℃

Storage temperature

-35℃~60℃



Partial Discharge Tester