Resonant Test System

Resonant Test System
Resonant Test System

Variable frequency series high voltage ac resonant test system Introduction

ZCVF-A series frequency conversion series resonant AC withstand voltage device is suitable for AC withstand voltage test of transformer, circuit breaker, switch, GIS system, cable, bushing, insulator and other equipment. It has the functions of high voltage over-voltage protection, low voltage over-current protection, detuning protection, zero position protection, flashover protection, emergency shutdown, under-voltage protection and so on. It not only meets the requirements of equipment test conditions for high voltage and small current, but also meets the requirements of equipment test conditions for low voltage and large current, and has a wide application range.

 

HV AC Frequency Series Resonant Test Set Features

1. The required power supply capacity is greatly reduced, and the power required for the test is only 1/Q of the test capacity.

2. Small size, light weight, generally 1/3-1/5 of the ordinary test device;

3. The resonant power supply is a resonant filter circuit, which can improve the waveform distortion of output voltage, obtain good

Sinusoidal waveform, and effectively prevent the wrong breakdown of the sample by harmonic peak value.

4. Variable-frequency power supply has strong protection function and good stability. It has automatic (automatic tuning, automati

boosting), full manual (manual tuning, manual boosting) and semi-automatic (automatic tuning, manual boosting and manual tuning,automatic boosting) working modes, which can be switched over and used arbitrarily and operated conveniently. 220V or 380V single-phase power supply is used to facilitate on-site power access.

5. Flexible configuration, strong expansion function. The resonant reactor adopts multi-mode, building block combination, can be series and parallel, which meets the test requirements of a variety of samples and is more convenient for field use.

6. Large screen touch LED LCD color screen and external mouse directly complete the setting of various parameters. The test results can be saved, printed, uploaded, and retrieved and so on.

7. The frequency regulation of ZCVF-A series frequency conversion series resonant AC withstand voltage device can be divided into coarse tuning and fine tuning, and the test resonant point can be automatically found to ensure that the resonant frequency does not drift during the whole test process; the required power supply capacity is small, the power required for the test is only 1/Q of the test capacity the volume is small, the weight is light, and the resonant power supply is 1/3-1/5 of the ordinary test device; the resonant power supply resonant type. The filter circuit can improve the waveform distortion of the output voltage; obtain good sinusoidal waveform, effectively prevent the wrong breakdown of the sample by harmonic peak value; has a variety of working modes, using 220V or 380V single-phase power supply to facilitate on-site power supply; multi-mode, building block combination, can be operated in series and parallel, easy to use in the field.

 

Product Parameters

Rated output voltage

0~   1000kV and below

Output frequency

30 ~   300Hz

Resonant Voltage Waveform

Pure   sine wave, waveform distortion rate1.0%

Working hours

Full   Power Continuous Working Time: 60min

Quality factor

30~ 90

Frequency regulation sensitivity

0.1Hz

Instability

<   0.05%

Working power supply

Single   phase 220V or 3 phase 380V+ 10%

Power   frequency 50Hz+5%

Type

Variable   frequency power

supply

Resonant   reactor

Excitation   transformer

Divider

Scope of   application

ZCVF-A-54/54

 

3kW

 

27kV/1A   2sets (dry type)

 

3kVA   (dry type)

 

60kV

1000kVA   and below 10kV power

transformer   10kV switches and busesPT

CT etc.   10kV (300mm2) cables 1.0km

 

ZCVF-A-108/108

 

 

 

5kW

 

27kV/1A   4sets (dry type)

 

5kVA   (dry type)

110kV

31500kVA   and below 35kV power transformer 35kV switches and buses ,PTCT etc.   10kV (300mm2) cable 2km

35kV   (300mm2) cable 0.5km

ZCVF-A-200/200

 

10kW

 

50kV/1A 4sets   (dry type)

10kVA   (dry type)

 

200kV

50000kVA   and below 110kV power transformer 110kVGISPTCT etc. (Preventive   test) 35kV (300mm2) cables 1.0km 10kV (300mm2) cables2.0k

ZCVF-A-270/270

 

15kW

 

45kV/1A   6sets (dry type)

15kVA   (dry type)

 

300kV

50000kVA   and below 110kV power transformer 110kVGISPTCT etc. 35kV   (300mm2) cable 1.2km

10kV   (300mm2) cables 3.0km

ZCVF-   A-800/400

 

30kW

 

50kV/2A   8sets (dry type)

100kV/2A

4sets   (oil type)

30kVA   (dry type)

 

400kV

80000kVA   and below 220kV power transformer 50000kVA and below 110kV|

power transformer   110kV/220kVGISPT

CT etc.   35kV (300mm2) cable s2.0km

110kV   (300mm2) cable 0.7km

ZCVF-A-1600/800

 

60kW

 

200kV/2A   4sets (oil type)

 

60kVA   (dry type)

 

800kV

80000kVA   and below 220kV power

transformer   50000kVA and below 1 10kV

power   transformer 500kVGISPT CT etc.

220kV   switchesGIS PTCT ect.

110kV   (400mm2) cables 1.5km

220kV   (400mm2) cable 1.0km


Why Choose us?

1. Owning advanced equipment and technology with our own Technology Dept.;

2.Good quality can be ensured by our Professional QC team with competitive price.

   State Grid Corporation of China is one of our customer!

3.Certifications are available.

4.OEM Service Offered.

5.Design Service Offered.  

6.Small trial order can be accepted to see our quality and service.

7. Standardization, effectiveness and timeliness of the pre-sale, in-sale and after sales service.



Resonant Test System