CT Parameter Analyzer

CT Parameter Analyzer
CT Parameter Analyzer

CTA-1000C CT Analyzer is mainly used for field testing, it can finish the measurements (M) and protection (P) class CT, PT and TYP class CT. Adopt LCD, self-equipped mini type printer supporting field printing; supporting to use USB flash disk to dump data, with simple and convenient operation.


small size




Why Choose us?

1. Owning advanced equipment and technology with our own Technology Dept.;

2.Good quality can be ensured by our Professional QC team with competitive price.

   State Grid Corporation of China is one of our customer!

3.Certifications are available.

4.OEM Service Offered.

5.Design Service Offered.  

6.Small trial order can be accepted to see our quality and service.

7. Standardization, effectiveness and timeliness of the pre-sale, in-sale and after sales service.

FUNCTION

I. Current Transformer (CT)II. Voltage Transformer (PT)
1. Magnetization curve1. Excitation characteristic test
2. Transformation ratio test2. Transformation ratio test
3. Polarity3. Polarity
4. 5% and 10% error curve4. Ratio error, phases
5. Current Injecting5. Degauss
6. Degauss6. Calculation of knee point value
7. Ratio error, phases7. Actual secondary load (burden), test (burden)
8. Automatic calculation of excitation knee point value8. Resistance test
9. Actual secondary load test (burden) (load test)
10. Resistance test
11. Secondary winding time constant (Ts)
12. Remanence coefficient (Kr)
13. Transient dimensioning factor (Ktd)
14. Peak instantaneous error (Er)
15. Magnetizing inductance (LU)

Parameters

Electrical parameters

Accuracy

0.05%, 0.1%

Power supply

AC 220V±10% or AC 110V±10%, 50/60Hz

Excitation output voltage

0-220Vrms

Excitation output current

0-5Arms (20A peak-value)

Automatic frequency variation range

0.1-60Hz

Equivalent excitation voltage

≤5000V

Accuracy

≤0.5% (0.2%RD+0.3%RG)

Secondary winding DC resistance   measurement

Range

0.1-300Ω

Accuracy

≤0.5% (0.2%RD+0.3%RG)

Secondary actual load measurement

Range

5VA-1000VA

Accuracy

≤0.5% (0.2%RD+0.3%RG)±0.1VA

CT/PT phase error measurement

Accuracy

±4min

Resolution

0.01min

CT ratio error measurement

Range

1-30000

Accuracy

≤0.5%

PT ratio error measurement

Range

1-10000

Accuracy

≤0.5%

Mechanical parameters

Overall dimension (L x W x H) (mm)

365 x 165 x 300 

Weight (kg)  

≤10 

Environmental conditions

Relative humidity   

90RH%

Operating temperature

-10°C to +40°C

Altitude

≤2000m

Main functions

The test items mainly include

Steady

Transient

excitation characteristic

secondary winding time constant   (Ts)

transformation ratio

remanence coefficient (Kr)

polarity

transient dimensioning factor (Ktd)

ratio error

peak instantaneous error (Er)

phases

magnetizing inductance (LU)

5% and 10% error curves

other parameters

resistance

secondary load



CT Parameter Analyzer