Oil Gas Chromatograph Analyzer

Oil Gas Chromatograph Analyzer
Oil Gas Chromatograph Analyzer

Introduction

The main technical index is ul/L (ppm):

H2< 2,CO<2,CO2<2,CH4 <0.1,C2H4<0.1,C2H6<0.1,C2H2<0.1


Implementation standards:

IEC567:1992 "insulation detection method of dissolved gas components in oil gas chromatography"

IEC60599:1999 "transformer oil dissolved gas analysis and judgment guide"

DL/T 722-2000 "transformer oil dissolved gas analysis and judgment guide"


Features

1.To achieve real-time computer control and data processing:

Instrument with digital interface, realize real-time data signal acquisition, data processing and test results on the computer through a communication line. Instruments and computers connected to the Internet can be connected by remote computers and instruments to realize remote data acquisition and management. The degree of freedom of the device is improved, and the effective application of the laboratory is promoted.

Through humanized software interface, greatly facilitate the user set including various temperature; intuitive operation including FID (first ignition has been changed fully automatically, without manual operation), open and close the switch bridge flow, temperature control, and each time events etc.


2Double stable high precision gas path control system.

◇ The gas path system stability dual carrier gas lines by stabilizing the current.

◇ Flow regulating valve with knob adjustment, intuitive, good reliability.

◇ Each pressure is displayed on the pressure gauge.


4. Hydrogen flame ionization detector (FID):

Cylindrical collector structure design, metal nozzle, high response

The detection limit is less than: 2 * 10-12g / S (sixteen n/ isooctane)

Baseline noise less than: 2* 10-13A

Baseline drift is less than: 2 * 10-12A/30min

Linear:≥106

Automatic ignition mode

Stable time: 10 minutes


5Large screen LCD display:

Clearly show the various temperature setting value, measured value and protection value Real-time display instruments

Touch type keyboard, menu operation, and automatic ignition


6Temperature control index:

◇ Temperature: room temperature of 5 DEG ~420 DEG precision - 0.1 DEG C


7Other parameters:

◇ Power: 220V + 22V, 50Hz,

◇ Power: 2 kW

◇ Weight: 55 KG

◇ Size: 60cm * 50cm * 50cm



Oil Gas Chromatograph Analyzer