CT Analyzer

CT Analyzer
CT Analyzer

CTA-1000 CT Analyzer automatically determines all relevant current transformer values and compares the results with the selected standard. The device evaluates the current transformer as per the IEC or IEEE standard within seconds with the push of a button.

It facilitates fast and economical on-site testing and calibration of metering and protection current transformers. Manufacturers of current transformers, high voltage transformers and switchgear also use the CT Analyzer for tests during development and production.

1


Product Advantage

 ● Easy to use: evaluates the current transformer within seconds with the push of a button;

  ● Highest measurement accuracy: 0.05% / 2 min when calibrating on site;

  ● According to IEC and IEEE standards;

  ● duration of the automatic test < 2min;

  ● Safety - Tests run at max. 180V;

  ● Very small and lightweight (<9kg /19.8lbs);

  ● easy to carry, anti-vibration.


Product Parameters


Type

CTA-1000C

Usage

CT, PT

Output

0~180Vrms,   12Arms, 36A(peak value)

Voltage   measurement accuracy

±0.1%

CT Ratio

Range

1~40000

accuracy

±0.05%

PT Ratio

Range

1~40000

accuracy

±0.05%

Phase

Range

±2min

accuracy

0.5min

DC   resistance

Range

0~300Ω

accuracy

0.2%±2mΩ

Burden

Range

0~1000VA

accuracy

0.2%±0.02VA

Power   supply

AC220V±10%,   50Hz

Environmental   Conditions

Operating   temperature : -10οC~50οC

Humidity   :≤90%

Weight   and Dimensions

Dimensions:   365 mm×290mm×153mm;

Weight<10kg



Product Upgrade

The equipment supports U disk upgrade. Our company only needs to send the updated  program to  the customer, who can upgrade through U disk and we will show the upgraded video to the customer.

6



CT Analyzer