30kV Very Low Frequency Cable Testing VLF High Voltage Generator

30kV Very Low Frequency Cable Testing VLF High Voltage Generator
30kV Very Low Frequency Cable Testing VLF High Voltage Generator

Ultra-Low Frequency Products and Selection of It

1、0.1Hz -30KV Ultra-Low Frequency High Voltage Generator

Table 1

Model

Rated Voltages

Load capacity

Fuse

Weight

Useful

VLF-30/1.1

30kV

(peak )

0.1Hz,≤1.1µF

10A

Control :6㎏

Body Boost :30㎏

10KV Cables、Generator

0.05Hz,≤2.2µF

0.02Hz,≤5.5µF


2、How to choose the suitable products for test

Please make sure that the capacitance of test products is below the instrument rated capacitance. The waveform will be influence if the capacitance of test products is too small and the instrument can not normally output when it below 0.05µF. 0.1µF capacitor in parallel to auxiliary output. 

Below is capacitance of some instrument for your reference. Single relatively power capacity of different Generator.

   

Table 2


Thermal Power

Hydropower

Generator capacitance

(MW)

200

300

600

85

125-150

300

400

Single relatively

power capacity(µF)

0.2-0.25

0.18-0.26

0.31-0.34

0.69

1.8-1.9

1.7-2.5

2.0-2.5

Power capacitance of single-core XLPE insulated cable (µF/km)



Table 3


Capacity µF/Km

Voltage (kV)

10

0.15

0.17

0.18

0.19

0.21

0.24

0.26

0.28

0.32

0.38

-

35

-

-

-

0.11

0.12

0.13

0.14

0.15

0.16

0.17

0.19

Cross-sectional

area (cm²)

16

25

35

50

70

95

120

150

185

240

270



Products Introduction 

This product combines the advanced technology of modern digital conversion, fully computer control, automated boost, buck, measurement and protection. human intervention can cared out during the automatic step-up process , mains advantage includes fully electronic ,small sizes and light weight , large-screen LCD ( clear and intuitive ) , printer output test report , easy to use . designed to fully meet the power industry standards .mechanical approach are widely use for modulation and demodulation ultra-low-frequency signals but no standard sine wave , some error of measuring and spark discharge in high-pressure part etc, the products can overcome the shortcoming of above and the following features need to indicate in particular: 

Data of current and voltage are obtained directly through the sampling of high-pressure side and it is true and accurate. Over-voltage protection: the instrument will shut down to protection within 20 ms when the output voltage is exceeding limiting values of setting. 

Over-current protection: design for dual protection of high and low voltage, downtime protection can be accurately set in high-pressure side. Shut down to protection times is within 20 ms when the current of low-voltage sides exceeds reacted current. 

High-voltage output protection resistor design in the body boost and it is no need to additional outside resistor. Closed-loop negative feedback control circuit of high and low voltage.


Technical Parameter 

1、output rated voltage , Table 1 for reference 

2、output frequency :0.1Hz、0.05Hz、0.02Hz。 

3、loading capability : Table 1 for reference 0.1 Hz maximum 1.1µF 0.05 Hz maximum 2.2µF 0.02 Hz maximum 5.5µF 

4、accuracy :± (3% of full scale +0.5 KV)

 5、voltage waveform distortion :≤5% 

6、condition of use : indoor, outdoor; temperature : -10℃∽+40℃;humidity :≤85%RH

7、power supply :AC50 Hz,220V ±5%

8、power fuse : Table 1 for reference



30kV Very Low Frequency Cable Testing VLF High Voltage Generator