Secondary Injection Relay Test Kit

Secondary Injection Relay Test Kit
Secondary Injection Relay Test Kit

Secondary Injection Relay Test Kit Brief Introduction

Six phase voltage and six phase current can be output, which has made it is possiable to be any combition, such as the output mode of the combination of conventional four phase current and three-phase current, six phase voltage mode, six phase current mode and 12 phase output mode. It not only can be compatible with the traditional way of various tests, but also can conveniently carry out differential test of three-phase transformer.


Secondary Injection Relay Test Kit play a key role in operating electricity power systems reliably and safely. It is the testing device used in professional field of microcomputer protection, relay protection, excitation measurement, fault recorder.


Secondary Injection Relay Test Kit Technical Data

 AC current source:

Amplitude range

6*(0~30A)/phase

accuracy: 0.5%

6 phase in parallel max output180A 
Phase current values allowed to work a long time 10A 
Power 300VA/phase 
6 phase in parallel max output power900VA
6 phase in parallel current max output allowable working time10s
Frequency range

0~1000Hz;

accuracy: 0.001Hz

Overtone order

2~20; phase :0~360°;

accuracy: 0.1°

 

DC current source:

Amplitude range20A/phase
Power300VA/phase
Accuracy0.5%

 

AC voltage source:

Amplitude range6*(0~125V)/phase, accuracy: 0.5%
Line voltage range0~250V
Phase voltage / Line voltage output power 750VA/100VA
Frequency range 0~1000Hz accuracy: 0.001Hz 
Overtone order 

2~20; phase :0~360°;

accuracy: 0.1°

 

 

DC voltage source:

Phase voltage output range0~±150V 
Accuracy 0.5% 
Line voltage output range 0~±300V 
Phase voltage / Line voltage output power 90VA/180VA 

 

Switch terminal:

Switch input terminals8 pairs
Dead contact1-20mA, 24V active output inside the device
Potential flip0--6V DC low level; 15-250V DC high level
Switch output terminals4 pairs, dead contact, rupturing capacity: 110V/2A, 220V/1A

 

Time measurement range:

Range1ms~9999s
Accuracy  1ms

 

Dimension & weight of the Secondary Injection Relay Test Kit:

Dimension455*530*220mm
Weight32Kg

20201127140259fbb1d63dabed46c994aece309b6bcddb





Secondary Injection Relay Test Kit