SF6 Gas Decomposition Analyzer

SF6 Gas Decomposition Analyzer
SF6 Gas Decomposition Analyzer

ZC-317D SF6 Gas Decomposition Analyzer

ZC-317D SF6 Gas Decomposition Analyzer also called SF6 Gas Decomposition Tester, it uses the world's most advanced UK Alpha high-performance, high resolution electrochemical sensors, embedded computer technology, is high-precision intelligent instrumentation.

By detecting SF6 insulating material inside the device main cleavage product -SO2, the content of H2S, HF and CO , can quickly and accurately determine the early failure SF6 circuit breakers, transformers , GIS, busbars, bushings and transformers and other electrical equipment inside for electric power, railway , metallurgy and petrochemical industries.


ZC-317D SF6 Gas Decomposition Analyzer Features

Simultaneously measure and respectively display the typical decomposition products

High precision, good stability, minimum tested quantity can be low as 0.1µl/L

Fast testing speed, can finish within 1 minute

Fault diagnosis and suggestion function, data management function, gas flow rate can be regulated and displayed

Simple operation, intuitive interface, self-contained power supply, No need calibration within 1 year

Eco-friendly, little gas consumption: 200~300ml for each time measuring

Decomposition products: SO2, H2S ( CO, HF optional)


Main Features

1. Measuring range

Decomposition products : H2S: 0 ~ 100 ppm (μL / L) ( standard ) ( not long-term than 200PPM)

SO2: 0 ~ 100 ppm (μL / L) ( standard ) ( not long-term than 200PPM)

CO: 0 ~ 500 ppm (μL / L) ( optional ) ( not over a long 1000PPM)

2. Resolution : 0.1 ppm (μL / L)

3. Accuracy : SO2, H2S: 5 ~ 20 ± 1 ppm (μL / L) 20 ~ 100 ± 3 ppm (μL / L)

CO: 5 ~ 50 ± 3 ppm (μL / L) 50 ~ 200 ± 10 ppm (μL / L)

4. The limit of detection : SO2: ≤0.1 ppm (μL / L)

H2S: ≤0.1 ppm (μL / L)

CO: ≤1 ppm (μL / L)

5. Repeatability: <± 2%

6. Measurement time: about 3 minutes

7. A sampling: built-in flow valve, electronic mass flow meter, 5 m sampling tube and pipe two meters out.

8. Sampling flow : 0.15 ~ 0.3 l / min

9. Working temperature : -20 ℃ ~ + 50 ℃

10. Sampling: quick connectors, PTFE tube extension, built-in electronic flow meter

11. Operating temperature : -20 ℃ ~ 50 ℃

12. Power Source: AC and DC ; once fully charged can work continuously for eight hours , AC : 220V / 50Hz

13. Display: Large color touch screen LCD display with a resolution of 800 × 480;

14. Input: High sensitivity touch screen

15. Output interface: USB 2.0;

16. Storage: with a storage capacity of thousands of pieces of data , with automatic storage function , can also be manually store the current test data

17. Volume weight: 320 × 270× 140 (mm)



SF6 Gas Decomposition Analyzer